HMO Fire Safety Regulations: What Landlords in England Must Do

There is no single HMO fire law. Four main overlapping regimes set the duties, from a recorded fire risk assessment to alarms and escape routes. Here is what each requires.

Never miss a renewal

LLCR tracks your compliance deadlines and reminds you before they expire. One place for your whole portfolio.

Track your first property free

No payment card. First property stays free.

Fact-check: unresolved

  • Re-check verdict was FIX on one item: the Summary said "Four overlapping regimes" while the opening says "mainly four". The checker's exact correction ("Four main overlapping regimes") has been applied; no third check was run under the one-fix-round rule. Delete this block and set Status to Published once you are happy.

There is no single "HMO fire regulation" in England. Fire safety duties in a house in multiple occupation come mainly from four overlapping sources: the Regulatory Reform (Fire Safety) Order 2005, regulation 4 of the Management of Houses in Multiple Occupation (England) Regulations 2006, the Smoke and Carbon Monoxide Alarm (England) Regulations 2015, and the mandatory conditions in Schedule 4 to the Housing Act 2004 for licensed HMOs. Fire hazards under the HHSRS and, in some buildings, the Fire Safety (England) Regulations 2022 can also apply.

This article is for general information purposes only and does not constitute legal advice. Landlords should seek independent legal advice for their specific circumstances. It describes the position in England.

Which fire safety laws apply to an HMO?

Each regime has its own scope, its own enforcer and its own penalty, which is why landlords who comply with one often miss another. The table below sets out the main sources.

SourceWhat it requiresWho enforces it
Regulatory Reform (Fire Safety) Order 2005A suitable and sufficient fire risk assessment of the shared parts, recorded in writing, and the general fire precautions it identifiesFire and rescue authority
Management of HMOs (England) Regulations 2006, reg. 4Escape routes kept clear and in repair; fire alarms and firefighting equipment maintained; escape notices displayed (5 or more occupiers)Local housing authority
Smoke and Carbon Monoxide Alarm (England) Regulations 2015, reg. 4A smoke alarm on every storey with living accommodation; a CO alarm where there is a fixed combustion appliance other than a gas cookerLocal housing authority
Housing Act 2004, Schedule 4 (licensed HMOs)Licence conditions on smoke and CO alarms, gas and electrical safety, and declarations on demandLocal housing authority
Housing Act 2004, Part 1 (HHSRS)"Fire and explosions" is one of the hazards councils assess in any rented home, including inside individual roomsLocal housing authority

The 2006 Management Regulations apply to every HMO in England, licensed or not, but they do not apply to converted blocks of flats that are HMOs under section 257 of the Housing Act 2004. Our guide to the HMO management regulations covers the non-fire duties in the same regulations.

Does an HMO legally need a fire risk assessment?

In most HMOs, yes. Article 9 of the Fire Safety Order requires the responsible person, meaning the person in control of the premises in connection with a business (in a let HMO, usually the landlord, licence holder or a managing agent with control), to make a suitable and sufficient assessment of the fire risks and review it regularly.

The Order does not apply to "domestic premises", which article 2 defines as premises occupied as a private dwelling, including appurtenances such as a garden or yard that are not used in common by the occupants of more than one dwelling. Parts shared between separate dwellings are therefore not "domestic premises", which is why the Order bites on the shared parts of an HMO: hallways, stairs, landings and other common escape routes. In a bedsit-style HMO where each occupier has their own unit of accommodation, the shared parts fall squarely within it.

The position is less settled for a small shared house let to a group of sharers on one tenancy. The LACORS guidance takes the view that the Order does not apply to a shared house let as a whole to a group of sharers on one tenancy, because the occupiers have exclusive use of the whole house. Each case turns on its facts, and the Housing Act duties discussed below still apply in full. Given that uncertainty, landlords are generally advised to carry out and record an assessment for every HMO.

What changed in October 2023?

Before 1 October 2023, the duty to write down the findings of an assessment applied only in limited cases, such as where five or more people were employed or a licence was in force. Section 156 of the Building Safety Act 2022 changed article 9(6) so that, from 1 October 2023, every responsible person must record the assessment. Some online guidance still describes the old rule and is out of date.

The record must include the findings of the assessment, the measures taken or planned, and any group of people identified as especially at risk (article 9(7)). The assessment must be reviewed regularly and in particular after a significant change, such as a new layout, a conversion or a change in occupancy.

What does regulation 4 of the HMO Management Regulations require?

Regulation 4 places four safety duties on the manager of every HMO it covers, three of them specifically about fire:

  • All means of escape from fire must be kept free from obstruction and maintained in good order and repair (reg. 4(1)).
  • Any firefighting equipment and fire alarms must be maintained in good working order (reg. 4(2)).
  • Notices showing the location of the means of escape must be displayed where occupiers can clearly see them (reg. 4(3)). This duty does not apply where the HMO has four or fewer occupiers (reg. 4(6)).
  • The manager must take all reasonable measures to protect occupiers from injury, having regard to the design, structural condition and number of occupiers (reg. 4(4)).

A bicycle stored in a protected stairway, or a fire door wedged open, is likely to breach regulation 4(1) as well as being a fire risk. Escape routes are a routine focus of council inspections.

How many smoke and carbon monoxide alarms does an HMO need?

The legal minimum is set by regulation 4 of the Smoke and Carbon Monoxide Alarm (England) Regulations 2015, as amended from 1 October 2022. A relevant landlord must ensure:

  • a smoke alarm on each storey with a room used wholly or partly as living accommodation (a bathroom or lavatory counts as such a room);
  • a carbon monoxide alarm in any room used as living accommodation that contains a fixed combustion appliance other than a gas cooker;
  • alarms are checked and in working order on the day a new tenancy begins; and
  • an alarm reported as faulty is repaired or replaced as soon as reasonably practicable.

For licensed HMOs, paragraph 1(4) and (4A) of Schedule 4 to the Housing Act 2004 repeat these requirements as mandatory licence conditions and add a duty to give the council, on demand, a declaration about the condition and positioning of the alarms. The detail is in our article on smoke and carbon monoxide alarm regulations.

The legal minimum is rarely what a council expects in an HMO. Councils commonly assess fire detection, fire doors, escape routes and emergency lighting against the LACORS guidance Housing – Fire Safety (2008), which sets benchmark standards by type and size of property and refers to the alarm grades and categories in BS 5839-6. That guidance is not law, but it is widely used to judge whether the fire hazard has been adequately addressed and to set licence conditions.

Do the Fire Safety (England) Regulations 2022 apply to HMOs?

They can. Regulation 9 of the Fire Safety (England) Regulations 2022 applies to any building containing two or more sets of domestic premises with common parts residents would use to evacuate. It requires the responsible person to display fire safety instructions, give a copy to new residents as soon as reasonably practicable, and reissue them every 12 months.

That plainly covers a section 257 HMO, meaning a building converted into self-contained flats where the conversion work did not meet the appropriate building standards and still does not, and less than two-thirds of the flats are owner-occupied. Whether a bedsit HMO with shared facilities counts as containing "two or more sets of domestic premises" is less clear, so landlords of those properties may wish to take advice or follow the instructions duty as good practice.

What are the penalties for HMO fire safety failures?

Penalties differ by regime, and a single failing can engage more than one. The figures below are maximums; the actual sum depends on the circumstances.

BreachLegal basisMaximum consequence
Fire Safety Order duty that puts people at risk of death or serious injuryFire Safety Order, art. 32(1)(a) and (3)On summary conviction, an unlimited fine; on indictment, an unlimited fine, up to two years' imprisonment, or both
Breach of the HMO Management RegulationsHousing Act 2004, s.234Prosecution, or a civil penalty of up to £40,000 under s.249A
Breach of an HMO licence conditionHousing Act 2004, s.72(3)Prosecution, or a civil penalty of up to £40,000 under s.249A
Failure to comply with an improvement notice on a fire hazardHousing Act 2004, s.30Prosecution, or a civil penalty of up to £40,000 under s.249A

The £40,000 cap in section 249A(4) applies to conduct on or after 1 May 2026, under the Financial Penalties (Housing Offences and Breach of Banning Orders) Regulations 2026 (SI 2026/319). Before that date the cap was £30,000. Operating a licensable HMO without a licence, and failing to comply with an improvement notice, can also expose a landlord to a rent repayment order. Our civil penalties table sets out the wider picture.

HMO fire safety checklist for landlords

  1. Confirm whether the property is an HMO and whether it needs a licence; our mandatory HMO licensing threshold article explains the test.
  2. Carry out, or commission, a fire risk assessment of the shared parts and record it in full.
  3. Diarise a review date, and review sooner after any change in layout, occupancy or use.
  4. Check smoke and CO alarms against the 2015 Regulations, then against what your council and the assessment expect.
  5. Walk the escape route: clear of storage, fire doors closing fully, escape notices displayed where there are five or more occupiers.
  6. Keep test and servicing logs for alarms, emergency lighting and firefighting equipment.
  7. If the building has two or more sets of domestic premises, issue fire safety instructions to residents and refresh them annually.
  8. File every certificate, log and remedial invoice with its date, so it can be produced on request.

Keeping the evidence in one place

Most HMO fire safety enforcement turns on records: whether an assessment exists, when it was last reviewed, and whether alarms and equipment were tested. The LLCR platform holds each property's documents in a document vault, tracks renewal and review dates, and logs hazards and the action taken in its issues and hazards register. Each upload and action is recorded on a dated audit trail. LLCR is free for one property.


Not sure whether your HMO paperwork would stand up to a council inspection? The free LLCR compliance checker takes a few minutes and shows where the gaps are.

Frequently asked questions

Does a small HMO need a written fire risk assessment?

Where the Regulatory Reform (Fire Safety) Order 2005 applies to the shared parts, yes. Since 1 October 2023, article 9(6) requires every responsible person to make a record of the assessment, replacing the old rule that only certain premises had to write their findings down. Whether the Order reaches the shared areas of a small shared house let on one tenancy is doubtful: the LACORS guidance says the Order does not apply to such shared houses, so many councils advise recording an assessment for every HMO regardless.

How many smoke alarms does an HMO need by law?

The Smoke and Carbon Monoxide Alarm (England) Regulations 2015 require at least one smoke alarm on every storey with a room used as living accommodation, and licensed HMOs carry the same requirement as a licence condition. In practice, councils usually expect more than the legal minimum in an HMO, often an interlinked system, based on LACORS guidance and the fire risk assessment.

How can I show a council my HMO fire safety is up to date?

Keep dated evidence of each duty: the recorded fire risk assessment and its reviews, alarm and emergency lighting test logs, servicing certificates and any remedial work. The LLCR platform stores these documents against the property with their dates and keeps a timestamped audit trail, so the record can be produced quickly if a council or fire officer asks for it.